Rectifier – GE Industrial Solutions GPS4827 User Manual

Page 89

Advertising
background image

Galaxy Power System GPS4827

87

Rectifier

Rectifier Specifications

Electrical

Input

Voltage Range

95-275Vac, 2-wire, single phase

Frequency Range

45 - 66 Hz

Power Factor

> 0.98 at > 50% rated output

AC Surge Protection: It is important that ac surges reaching rectifiers do not exceed the capacity of the
rectifier internal surge protection. Protection must be provided external to the GPS system, if necessary,
to limit surge energy reaching the rectifiers. Site surge protection must be coordinated with rectifier
internal surge protection and must clamp at a lower voltage than the rectifier internal protection. The
internal protection voltage and current characteristics of the rectifiers are as follows:

Phase to Phase Voltage

MOV Conduction Current

320Vac (RMS)

0A

620V maximum clamping

1mA (DC test current)

810Vpeak

100A peak

Output

Internal Selective High Voltage Shutdown (ISHVSD)


High Voltage Shutdown (HVSD)

Float: 56.0Vdc Nom.

1,

2

Boost: 58.5Vdc Nom.

1,

2


Float: 57.00Vdc

Output

Output Power

2726W maximum

Output Current

1

50Adc maximum from -40°C to +55°C
30Adc at +75°C
Rectifier derates at approximately
1 ampere per degree C (+55°C to +75°C)

Float/Boost Voltage

44-58Vdc

Total Harmonic Distortion

<5% at full load

Regulation

±0.5%

Ripple

100 mVrms

Current Limit Set Point

15A-55A

1.

With Galaxy Millennium Controller

2.

Factory default settings – actual range is 44 - 58Vdc