81

The DIST and MAJ LEDs and Power Major and MJF alarm relays will be active.

Remove alarm condition and verify that DIST,MAJ LEDs and MJF relay retire.

Alarms should be tested in each distribution bay of the plant to verify the integrity of
the alarm bus throughout the plant.
If the distribution bays are equipped with “Bay Fuse Alarm” indicating LEDs, also verify
that this LED activates during these tests for the bay in which the alarm originates (and
not in any other).

.

Clear History

This feature is useful when there is a need to remove unnecessary historical data from
the controller. An example might be after installation and testing and the controller is
ready for operation. There may be history that is of no use to the customer. Also,
since the history log has a finite number of entries, user can save the history using a
PC, and then clear the logs.

Step

Action

1.

From the Default Screen, press the Menu button for the Main Menu.

2.

Using the Up/Down Arrows, Scroll to Control/Operations and press Enter.

3.

Select Clear History, and press Enter.

4.

Press Enter again to clear the History Log, or Escape to return to the menus.