57

Symbol

Default Designation

Default
Severity

Default LED Default Relay

ATF

Alarm Test Failed

Warning

None

None

BBL

Memory Backup Battery Low

Warning

None

None

BCA

Battery Type Conflict

Warning

None

None

BDA

Battery on Discharge

Major

BD

BD

BFA

Battery Test Failed

Minor

BAT

None

BID

Bay Interface ID Conflict

Major

CTLR

CTLR

BTA

Battery Test Active

RO

BD

BD

BTJ

Battery Thermal Major

Major

BAT

None

BTN

Battery Thermal Minor

Minor

BAT

None

CCH

Configuration Changed

RO

None

None

CDFA

Converter Distribution Fuse

Major

RECT

MJF

CDID

Converter ID Conflict

Major

RECT

None

CFA

Converter Fail

Minor

RECT

None

CLC

Clock Changed

RO

None

None

CMA

Minor Communications Failure Minor

CTLR

None

CMFA

Multiple Converter Fail

Major

RECT

None

CNF1

Contactor 1 Failed

Major

BAT

None

CNF2

Contactor 2 Failed

Major

BAT

None

CNF3

Contactor 3 Failed

Major

BAT

None

CNO1

Contactor 1 Open

Major

BAT

None

CNO2

Contactor 2 Open

Major

BAT

None

CNO3

Contactor 3 Open

Major

BAT

None

COF

Queue Overflow

Warning

None

None

COR

Number Did Not Respond

Warning

None

None

CPA

Circuit Pack Fail

Major

CTLR

CTLR

CRA

Controller Fail

Major

CTLR

CTLR

DID

Rectifier ID Conflict

Major

RECT

None

EMD

Energy Management Disabled Warning

None

None

EPD

Excess Plant Drain

Minor

RECT

None

EPO

Emergency Power Off

Critical

BATT

None

EPR

External Password Reset

Warning

None

None

ETO

Engine Transfer Timeout

Minor

AC

None

EXL

Excessive Login Attempts

Warning

None

None

FAJ

External Fuse Major

Major

DIST

MJF

FAN

External Fuse Minor

Minor

DIST

MNF

HCL

History Cleared

RO

None

None

Advertising