GE Industrial Solutions GPS4827 User Manual

Page 51

Advertising
background image

Galaxy Power System GPS4827

49

Rectifier Sequence Option
The controller is capable of sequencing rectifiers on line after detecting a AC is being
provided by emergency generator. Internal Rectifier Sequencing requires external
wiring to ETR/ETRR on BSL pin numbers 75/76, and optionally RO/ROR on BSL pin

numbers 77/78, in order to function.
The controller can also accept ground signals onto TR1 to TR4 on BSL 73/79/ 85/80
from an external device to control the sequencing of plant rectifiers in groups as
follows:

Table 9-D: TR leads and Associated Rectifiers

TR

Signal

Rectifiers Affected

TR1

G01, G02, G09, G10, G17, G18, G25, G26, G33, G34, G41, G42, G49, G50,
G57, G58

TR2

G03, G04, G11, G12, G19, G20, G27, G28, G35, G36, G43, G44, G51, G52,
G59, G60

TR3

G05, G06, G13, G14, G21, G22, G29, G30, G37, G38, G45, G46, G53, G54,
G61, G62

TR4

G07, G08, G15, G16, G23, G24, G31, G32, G39, G40, G47, G48, G55, G56,
G63, G64

Additional information on the Rectifier Sequence Options can be found in the User’s
Guide for Millennium II Controller Advanced Features manual.

Battery Temperature Option
Slope Thermal Compensation and Battery Reserve Time Prediction features of the
controller, require that battery temperature be monitored. If either of these features
is to be configured in Galaxy software, a battery temperature input must be
connected to P3 temperature probe connector on the Controller board.
Three optional cables are used to connect to various battery arrangements:

Cable Assembly

Connects to:

848152997

KS20472 round cell thermistor

848152989

ring or paddle type thermistors

848153003

210E Thermal Probe Multiplexer


Refer to User’s Guide for Millennium II Controller Advanced Features manual for
additional information on these features.

Alarm Battery Supply Signals

Table 9-E: ABS Pin Numbers

Signal Name

Pin No.

ABS

93

ABS

94

DG

95

DG

96