GE Industrial Solutions GPS4827 User Manual
Page 88
Galaxy Power System GPS4827
86
Cabinet Output -48V
1 or 2 x Full Height
Maximum System
Output Current
50 - 1800A
1800A @ 45
:C
Cabinet Mechanical
Full Height
Nominal Cabinet Dimensions
(H x W x D)
2134 H x 600 W x 600 D mm
(84 H x 23.6 W x 23.6 D in.)
Units Per Initial Cabinet
Rectifiers
1 - 36
Controller
1 per system
Battery Disconnect Modules
0 - 1
DC Distribution
1 – As many as will fit
Units Per Supplemental Cabinet
Rectifiers
1 – 12 (Maximum 36 rectifiers per system)
Battery Disconnect Modules
0 - 1
DC Distribution
1 – As many as will fit
Environmental
Operating Ambient
Temperature
0°C to +45°C
Altitude
-50 to 4000 meters
Note: For altitudes between 1500 and 4000 meters, derate the maximum
temperature by 0.656°C per 100 meters.
Humidity
5% to 95% non-condensing
Radiated and Conducted
Emissions
FCC Part 15, EN55022 (CISPR22), EN55024, Level A GR1089
Electromagnetic Immunity
Complies with GR1089
Earthquake Rating
Zone 4, upper floors
Standards Compliance
Agency Approvals
CE Marked, UL
Underwriters Laboratories (UL) 1950 Listed per Subject Letter S1801, DC Power
Distribution Centers for Telecommunications Equipment