GE Industrial Solutions GPS4827 User Manual

Page 88

Advertising
background image

Galaxy Power System GPS4827

86

Cabinet Output -48V

1 or 2 x Full Height

Maximum System

Output Current

50 - 1800A

1800A @ 45

:C

Cabinet Mechanical

Full Height

Nominal Cabinet Dimensions
(H x W x D)

2134 H x 600 W x 600 D mm
(84 H x 23.6 W x 23.6 D in.)

Units Per Initial Cabinet

Rectifiers

1 - 36

Controller

1 per system

Battery Disconnect Modules

0 - 1

DC Distribution

1 – As many as will fit

Units Per Supplemental Cabinet

Rectifiers

1 – 12 (Maximum 36 rectifiers per system)

Battery Disconnect Modules

0 - 1

DC Distribution

1 – As many as will fit

Environmental

Operating Ambient
Temperature

0°C to +45°C

Altitude

-50 to 4000 meters
Note: For altitudes between 1500 and 4000 meters, derate the maximum
temperature by 0.656°C per 100 meters.

Humidity

5% to 95% non-condensing

Radiated and Conducted
Emissions

FCC Part 15, EN55022 (CISPR22), EN55024, Level A GR1089

Electromagnetic Immunity

Complies with GR1089

Earthquake Rating

Zone 4, upper floors

Standards Compliance

Agency Approvals

CE Marked, UL
Underwriters Laboratories (UL) 1950 Listed per Subject Letter S1801, DC Power
Distribution Centers for Telecommunications Equipment