Galaxy Power System GPS4827
59
Table 9-K: Rectifier Alarm Defaults
Symbol
Default Designation
Default
Severity
Default LED Default Relay
ACF
AC Fail
Minor
AC
ACF
CLM
Rectifier Current Limit
RO
None
None
ERD
Excess Rectifier Drain
Minor
RECT
None
ETS
External Transfer Shutdown
Minor
RECT
None
HPA
Half Power
Minor
RECT
None
LCA
Low Current Alarm
Minor
RECT
None
LSF
Load Share Fuse
Minor
RECT
None
MACF
Multiple AC Fail
Major
AC
ACF
MAN
Manual Off
Minor
RECT
None
MFA
Multiple Rectifier Fail
Major
RECT
RFA
MMAN
Multiple MAN Alarm
Major
RECT
None
PHA
Phase Or Low Output
Minor
AC
None
RIC
Rectifier Incomplete Config
Warning
None
None
RFA
Rectifier Fail
Minor
RECT
RFA
Default Display
The default display shown in figure 4-8
provides basic system status. The controller
returns to this display after approximately three minutes after the last time a key is
pressed.
Figure 9-8:
Millennium II Controller Default Display
The first line shows:
# of Alarms
# of Warnings
Date
Time
The larger text in the middle of the screen shows:
Plant Voltage
Plant Load (Current)