7 wiring for 1600 a and 3200 a models, Iring, 1600 a – GE Industrial Solutions EPM1500 Single Point Submetering System User Manual

Page 18: 3200 a m, Odels

Advertising
background image

2–8

EPM 1500 SUB-METER – INSTRUCTION MANUAL

CHAPTER 2: INSTALLATION

2.2.7

Wiring for 1600 A and 3200 A Models

For the 1600 A and 3200 A models (order codes PL1500***SP162* and PL1500***SP322*),
the CT terminations are made on the HCA-2 module to allow the EPM 1500 to accept 5 A
secondary current inputs. CAREFULLY observe the following figure and terminate the CT
leads on the included HCA-2 module, NOT the fuse block.

FIGURE 2–6: CT Terminations for 1600 A and 3200 A Models

709717A1.CDR

Advertising