EPM 1500 SUB-METER – INSTRUCTION MANUAL
CHAPTER 2: INSTALLATION
2.2.7
Wiring for 1600 A and 3200 A Models
For the 1600 A and 3200 A models (order codes PL1500***SP162* and PL1500***SP322*),
the CT terminations are made on the HCA-2 module to allow the EPM 1500 to accept 5 A
secondary current inputs. CAREFULLY observe the following figure and terminate the CT
leads on the included HCA-2 module, NOT the fuse block.
FIGURE 2–6: CT Terminations for 1600 A and 3200 A Models
709717A1.CDR