GE Industrial Solutions EPM1500 Single Point Submetering System User Manual

Page 42

Advertising
background image

4–10

EPM 1500 SUB-METER– INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATIONS

0170

*

0368

Voltage (CT01)

R

V

Instantaneous Voltage

0172*

0370

Amps (CT01)

R

A

Instantaneous Current

0174*

0372

kW (CT01)

R

kW

Instantaneous Power

0176*

0374

kvar (CT01)

R

kvar

Instantaneous Reactive Power

0178*

0376

kVA (CT01)

R

kVA

Instantaneous Apparent Power

017A*

0378

Voltage (CT02)

R

V

Instantaneous Voltage

017C*

0380

Amps (CT02)

R

A

Instantaneous Current

017E*

0382

kW (CT02)

R

kW

Instantaneous Power

0180*

0384

kvar (CT02)

R

kvar

Instantaneous Reactive Power

0182*

0386

kVA (CT02)

R

kVA

Instantaneous Apparent Power

0184*

0388

Voltage (CT03)

R

V

Instantaneous Voltage

0186*

0390

Amps (CT03)

R

A

Instantaneous Current

0188*

0392

kW (CT03)

R

kW

Instantaneous Power

018A*

0394

kvar (CT03)

R

kvar

Instantaneous Reactive Power

018C*

0396

kVA (CT03)

R

kVA

Instantaneous Apparent Power

Three-Phase Metered Values

0288*

0648

3-Phase kWh

R

kWh

Real Time Input 1

028A*

0650

3-Phase kvarh

R

kvarh

Real Time Input 2

028C*

0652

3-Phase kW

R

kW

Real Time Input 3

028E*

0654

3-Phase kvar

R

kvar

Real Time Input 4

0290*

0656

3-Phase kVA

R

kVA

Real Time Input 5

0292*

0658

3-Phase Power Factor

R

%

Real Time Input 6

Total Harmonic Distortion (THD)

03E8*

1000

THD Phase A

R

%

Total Harmonic Distortion

03EA*

1002

Phase Angle A

R

degrees

Phase Angle

03EC*

1004

Phase-to-Phase Voltage A

R

V

Instantaneous Voltage

03EE*

1006

THD Phase B

R

%

Total Harmonic Distortion

03F0*

1008

Phase Angle B

R

degrees

Phase Angle

03F2*

1010

Phase-to-Phase Voltage B

R

V

Instantaneous Voltage

03F4*

1012

THD Phase C

R

%

Total Harmonic Distortion

03F6*

1014

Phase Angle C

R

degrees

Phase Angle

03F8*

1016

Phase-to-Phase Voltage C

R

V

Instantaneous Voltage

Counters

07D0

2000

Number of phases offset

16-bit Unsigned Integer

1, 2, 3, or 24 phases available

Table 4–1: Modbus Memory Map (Sheet 3 of 4)

Hex

Addr

Addr

Description

R/W

Units

Notes

Advertising