4 installing the pulse inputs, 1 pulse input option, Installing the pulse inputs -12 – GE Industrial Solutions EPM1500 Single Point Submetering System User Manual

Page 22: Ulse, Nput, Ption

Advertising
background image

2–12

EPM 1500 SUB-METER – INSTRUCTION MANUAL

CHAPTER 2: INSTALLATION

2.4

Installing the Pulse Inputs

2.4.1

Pulse Input Option

The EPM 1500 with the Pulse Input option will provide a 5-wire harness from the back of
the meter head. The color coding on the harness is as follows and the M# and Q# refers to
meter registers that will appear if the meter has pulse inputs:

• COMMON (WHITE)
• M2 Q14 (GREEN)
• M2 Q13 (ORANGE)
• M1 Q14 (RED)
• M1 Q13 (BLACK)