4 installing the pulse inputs, 1 pulse input option, Installing the pulse inputs -12 – GE Industrial Solutions EPM1500 Single Point Submetering System User Manual
Page 22: Ulse, Nput, Ption
Advertising
2–12
EPM 1500 SUB-METER – INSTRUCTION MANUAL
CHAPTER 2: INSTALLATION
2.4
Installing the Pulse Inputs
2.4.1
Pulse Input Option
The EPM 1500 with the Pulse Input option will provide a 5-wire harness from the back of
the meter head. The color coding on the harness is as follows and the M# and Q# refers to
meter registers that will appear if the meter has pulse inputs:
• COMMON (WHITE)
• M2 Q14 (GREEN)
• M2 Q13 (ORANGE)
• M1 Q14 (RED)
• M1 Q13 (BLACK)
Advertising