CHAPTER 4: COMMUNICATIONS

EPM 1500 SUB-METER– INSTRUCTION MANUAL

4–11

Note

1.

32-bit floating point numbers are as per the IEEE 754-1985 standard.

2.

Registers 0X0063 to 0X025E are all read-only and cannot be modified. They break
down as follows:

Registers 0X0064 to 0X0122 are not real-time, but are populated with
stored interval data based on user inputs to registers 0X0040 to 0X0043.

Registers 0X0162 to 0X025E are all real-time data registers.

07D1

2001

Demand Window Offset

16-bit Unsigned Integer

5, 15, or 30 minutes available

07D2

2002

I Multiplier Type Offset

16-bit Unsigned Integer

Internal calibration value

07D3

2003

Number of Pulse Counters Offset

16-bit Unsigned Integer

Number of external pulse inputs installed

07D4

2004

Overlap Offset

16-bit Unsigned Integer

Number of adjacent demand windows

that are averaged to determine peak

demand

07D5

2005

Number TOU's Offset

16-bit Unsigned Integer

Number of different TOU periods defined

in the time-of-use table

07D6

2006

MDT_M_TABLE_REG_START

16-bit Unsigned Integer

07D7

2007

NUM_MDT_M_TABLE_COLUMNS

16-bit Unsigned Integer

07D8

2008

NUM_MDT_M_TABLE_REGS

16-bit Unsigned Integer

07D9

2009

MDT_M_TABLE_REG_END

16-bit Unsigned Integer

* 32-bit floating point register.

+

32-bit long integer - Range: 00000000h to FFFFFFFFh

Table 4–1: Modbus Memory Map (Sheet 4 of 4)