CHAPTER 4: COMMUNICATIONS

EPM 1500 SUB-METER– INSTRUCTION MANUAL

4–9

0036

0054

Internal Time - Hours/Minutes

R/W hours/

minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF

0037

0055

Internal Time - Seconds

R/W month/day

0038

0056

Internal Date - Month/Day

R/W Year

16-bit Unsigned Integer

0039

0057

Interval Date - Year

R/W

16-bit Unsigned Integer

003A

0058

Date/Time of Oldest Interval -

Hours/Minutes

R/W Hours/

Minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

003B

0059

Date/Time of Oldest Interval -

Month/Day

R/W Month/Day

16-bit

Month: 1=Jan., 12=Dec. (bitmask = FF00)

Day: 1-31 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

003C

0060

Date/Time of Oldest Interval - Year R/W Year

16-bit Unsigned Integer

003D

0061

Date/Time of Newest Interval -

Hours/Minutes

R/W Hours/

Minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF)

003E

0062

Date/Time of Newest Interval -

Month/Day

R/W Month/Day

16-bit

Month: 1=Jan., 12=Dec. (bitmask = FF00)

Day: 1-31 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

003F

0063

Date/Time of Newest Interval -

Year

R/W Year

16 Bit Unsigned Integer

0040

0064

Date/Time of Currently Selected

Interval - Hours/Minutes

R/W Hours/

Minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF

0041

0065

Date/Time of Currently Selected

Interval - Month/Day

R/W Month/Day

16-bit

Month: 1=Jan., 12=Dec. (bitmask = FF00)

Day: 1-31 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

0042

0066

Date/Time of Currently Selected

Interval - Year

R/W Year

16 Bit Unsigned Integer

0043

0067

Data Ready Flag

R/W

16 Bits: Mask out/ignore Bit 15.

0=Data is ready for read

1=Populate registers with timestamp

data

2=Invalid Timestamp Requested

Stored Dynamic Data Ready for Read

3-Phase Totaled Values

0063

0099

Interval Data Qualifying Register

R

16-bit Unsigned Integer, 8 = Invalid

Interval

0064

0100

3-Phase Totaled kW

R

kW

Stored Interval 1

0066

0102

3-Phase Totaled kvar

R

kvar

Stored Interval 2

0068

0104

3-Phase Totaled kVA

R

kVA

Stored Interval 3

006A

0106

3-Phase Totaled Power Factor

R

%

Stored Interval 4

Metered Values

0162

0354

Frequency (Phase A)

R

Hz

Instantaneous Frequency

016A

0362

Voltage (A-N)

R

V

Instantaneous Voltage

016C

0364

Voltage (B-N)

R

V

Instantaneous Voltage

016E

0366

Voltage (C-N)

R

V

Instantaneous Voltage

Table 4–1: Modbus Memory Map (Sheet 2 of 4)

Hex

Addr

Addr

Description

R/W

Units

Notes

Advertising