CHAPTER 4: COMMUNICATIONS

EPM 1500 SUB-METER– INSTRUCTION MANUAL

4–5

Z

Check the Echo typed characters locally option, as shown below.

4.2.3

Confirming Connection to the EPM 1

500

Z

To confirm a proper RS485 connection to the EPM 1500, enter the
following command:

attn -D

(followed by the [ENTER] key)

If meter is properly connected, it will respond with a serial number and poll
address. Once in Modbus mode, this command will no longer work.
For example, entering the command

attn -D

followed by the [ENTER] key returns:

60005866 256

for a meter with serial number 60005866 and poll address 256.

4.2.4

Logging into the Meter

Use the following procedure to login to the EPM 1500.

Z

Setup a ‘key macro’ in HyperTerminal by selecting the View > Key
Macros
menu item.

Z

Click New and select an appropriate macro key sequence (ALT-1 is
used the example below.

Z

Enter the following command in the Action area:

attn -S[serialNumber] -5lEvElbAl<ENTER>

The password is -s5 followed by the LABLEVEL text spelled
backwards, with the vowels in upper case. This login string must
be followed by the ENTER command within the key macro.

Z

For example, for a unit with serial number 60005866, enter the
following text: