This is an example of the assignment of the drive parameters to the object

output data

and to the object

input data

with a32 Bit parameter.

Parameter A

Data Type: Unsigned32

Not used.
Not used.
Not used.

Object

subindex

Meaning of the object element

Byte number of the

input data

Process

Data

Channel

1

Length of the Process Data Channel

2

Index of the drive parameter A

1

32 Bit

3

4

Subindex of the drive parameter A

Not used.

Index = 0000

1

2

5

Not used.

Subindex = 00

2

6

Not used.

Index 0000

3

7

Not used.

Subindex = 00

3

8

Not used.

Index = 0000

4

9

Not used.

Subindex = 00

4

If the assignment of a drive parameter to the Process Channel is replaced with the assignment of a larger
parameter, the following Bytes of the object

Data Channel Descriptors, involved in the operation

must be cleared. If the assignment can not be correctly carried out , the response is negative.

IMPORTANT

In the current versions ot the

cards there is no control on the validity of the assignment of the

drive parameters to the Process Data Channel; the user, therefore, must control with care such assignment,

for example, the overlap of parameters or the overflow of the Process Data Channel capacities. In

the case these assignments are not carried out in a proper way, the system could behave in an unexpected

and potentially dangerous way.