2.7 Technical

The basic model of the Interbus-S interface card is called
According to the type of the drive connected, you can find several variants.
The card used must correspond to the specific drive.
The storage temperature is -20°C

and the operating one is 0°C

These are adequate to the

drive temperature they are connected to.

2 . 8

The card must be installed on the regulation card of the drive so that the

connector of the

cards is near the

connector of the regulation card, maintaining the link connectors to the line

INTERBUS-S in a downward direction. The tools provided with the card have to be used for the mechanical
connection. A 40 pin Flat Cable is necessary for the electric connection. As far as the connection to to the
Local Bus INTERBUS-S is concerned, you have to use the cables IBS PBC 100

or IBS PBC 150

m) which have to be linked to the connectors XIN and XOUT. If the device in use is the last of the Local Bus
line, the connector XOUT should not need to be linked to any cable.

The GND ground reference connection of the

card can be carried out through the terminal

PEG (ground), which has to be connected in one single point to the other PE terminals of the units belonging

to the same section of Local InterBus-S and to the PE terminal of the BK (Bus Terminal) modulus which

generates the local section of

The shield ground connection of the cables of the Local Bus Interbus-S can be carried out through the PES

terminal , which has to be connected in one single point to the other PE terminals of the units belonging to

the same section of Local InterBus-S and to the PE terminal of the BK (Bus Terminal) modulus which

generates the local section InterBus-S.