IPCP 505 • SIS Programming and Control

56

X6#

= Pulse time in 20 ms increments. If this parameter is

missing or = 0, then pulse length = default =

25 = 500 ms. 1 = 20 ms (minimum pulse time)

to 65535 = 1310700 ms (maximum pulse time).

X6(

= IP connection timeout period specified in

10-second steps (1 - 65000, default = 30 =

300 seconds). If no data is received during

the specified period, the Ethernet connection

closes. Responses are returned with leading

zeros.

X7)

= The number (0 - 65535) to insert into an

e-mail message if an *.eml file has

an embedded server-side include
“<!--#echo var = “WCR

|

” -->” (the

E

CR

}

command with no parameters)

The numeral is a 16-bit number to be employed

as the user defines.

This is an optional parameter. Use 0 as a
placeholder if the optional

X4&

variable is used

but

X7)

is not needed.

Maximum = 65535.

X7#

= An e-mail account username of up to 31

characters. Do not use commas. This parameter

is optional during setup and is used for SMTP

authentication.

X7$

= An e-mail account password (for SMTP

authentication) of up to 31 characters.

Do not use commas. This parameter is optional

during setup. If a password is set, the response

is not the actual password characters but

asterisks (****).

X8%

= Switched output power load status:

0 = ok (total power draw <40 watts)

1 = at limit (total power draw is 40-44 watts)

2 = fault/overload (total power draw >44 watts)

X8^

= Switched output power use:

total power drawn from all power output ports =

nnn, in tenths of watts

X8&

= Switched output power group:

0 = no group

1 = group 1

2 = group 2

X21)

= IR/serial port configuration type

0 = IR port (default, 0 – 5 VDC)
1 = RS-232 port (±5 VDC)

NOTE: For commands and examples of computer or device responses mentioned in this guide, the

character “0“ is used for the number zero and “O“ represents the capital letter “o”.