Totalizer analog input block – Fluid Components International ST100 Series Foundation Fieldbus User Manual

Page 19

Advertising
background image

ST100 Series Foundation Fieldbus

Fluid Components International LLC

17

INDEX

PARAMETER

DATA TYPE (LENGTH)

INITIAL VALUE

DESCRIPTION

23

ACK_OPTION

Bitstring(2)

24

ALARM_HYS

Float

25

HI_HI_PRI

Unsigned 8

26

H_HI_LIM

Float

27

HI_PRI

Unsigned 8

28

HI_LIM

Float

29

LO_PRI

Unsigned 8

30

LO_LIM

Float

31

LO_LO_PRI

Unsigned 8

32

LO_LO_LIM

Float

33

HI_HI_ALM

DS-71

34

HI_ALM

DS-71

35

LO_ALM

DS-71

36

LO_LO_ALM

DS-71

Totalizer Analog Input Block
This block takes the input data from the Process Data Transducer Block, selected by the “Totalizer Average Channel” and makes it available to other

function blocks at its output.

L_TYPE parameter
This parameter determines how the values passed by the Process Transducer Block will be used in the block. There are two options; direct or

indirect.

Direct

The Process Data Transducer Totalizer value is passed directly to the PV of this AI block, and the XD_SCALE information is not used.

Indirect The Process Data Transducer Totalizer value is converted to the OUT_SCALE and the information of XD_SCALE is applied.

CHANNEL parameter
This parameter selects the process variable to be used. The CHANNEL parameter, in the ST100 for the Totalizer Analog Input Block MUST be

set to “Totalizer Average”.

XD_SCALE parameter
This parameter sets the high and low scale values, the units index, and the number of digits after the decimal point, for display purposes.

ST100 Totalizer Analog Inupt Block
The table below summarizes the ST100 Totalizer Analog Input Block.

INDEX

PARAMETER

DATA TYPE (LENGTH)

INITIAL VALUE

DESCRIPTION

1

ST_REV

Unsigned 16

0

2

TAG_DESC

OctString(32)

Spaces

3

STRATEGY

Unsigned 16

0

4

ALERT_KEY

Unsigned 8

0

5

MODE_BLK

DS-69

O/S

6

BLOCK_ERR

Bitstring(2)

7

PV

DS-65

ST100 Totatizer value from the trasn-

ducer block