Pid block – Fluid Components International ST100 Series Foundation Fieldbus User Manual

Page 22

Advertising
background image

ST100 Series Foundation Fieldbus

20

Fluid Components International LLC

PID Block
This block offers control algorithms that use the Proportional, Integral and Derivative terms. The algorithm is non-iterative or ISA. In this algorithm

the GAIN is applied to all terms of the PID, and the proportional and the integral actuate over the error, and the derivative actuates over the PV value.

ST100 PID Block

INDEX

PARAMETER

DATA TYPE (LENGTH)

INITIAL VALUE

DESCRIPTION

1

ST_REV

Unsigned16

0

2

TAG_DESC

OctString(32)

Blanks

3

STRATEGY

Unsigned16

0

4

ALERT_KEY

Unsigned8

0

5

MODE_BLK

DS-69

OOS

6

BLOCK_ERR

Bitstring(2)

7

PV

DS-65

Bad ns 0

ns = non specific

8

SP

DS-65

G C/0

G C/0 = GOOD_CAS/0

9

OUT

DS-65

BOS

BOS = BAD_Out of service 0

10

PV_SCALE

DS-68

0-100%

11

OUT_SCALE

DS-68

0-100%

12

GRANT_DENY

DS-70

0,0

13

CONTROL_OPTS

Bitstring(2)

0

14

STATUS_OPTS

Bitstring(2)

0

15

IN

DS-65

BNc

BNc= Bad-Not connected 0

16

PV_FTIME

Float

0

17

BYPASS

Unsigned8

Unititialized

18

CAS_IN

DS-65

BNc

BNc= Bad-Not connected 0

19

SP_RATE_DN

Float

+INF

20

SP_RATE_UP

Float

+INF

21

SP_HI_LIM

Float

100

22

SP_LO_LIM

Float

0

23

GAIN

Float

0

24

RESET

Float

+INF

25

BAL_TIME

Float

0

26

RATE

Float

0

27

BKCAL_IN

DS-65

BNc

BNc = Bad_Not connected /0

28

OUT_HI_LIM

Float

100

29

OUT_LO_LIM

Float

0

30

BKCAL_HYS

Float

0.5%

31

BKCAL_OUT

DS-65

BNs0

BNs0 = Bad-Non Specific 0

32

RCAS_IN

DS-65

Bos0

Bos0=Bad-Out of Service/0

33

ROUT_IN

DS-65

Bos0

Bos0=Bad-Out of Service/0

34

SHED_OPT

Unsigned8

Uninitialized

35

RCAS_OUT

DS-65

BNs0

BNs0 = Bad-Non Specific 0

36

ROUT_OUT

DS-65

BNs0

BNs0 = Bad-Non Specific 0

37

TRK_SCALE

DS-68

0-100%