Configuring the flow ai block, Configuring the temperature ai block – Fluid Components International ST100 Series Foundation Fieldbus User Manual

Page 25

Advertising
background image

ST100 Series Foundation Fieldbus

Fluid Components International LLC

23

Configuring the Flow AI block

Double click on the “Flow” AI block.
If the MODE_BLK.TARGET of the AI block is not set to ‘OOS’, set it to ‘OOS’.

Note:

Some parameters can be written only if the MODE_BLK.

ACTUAL is set to ‘OOS’.

• Set the CHANNEL parameter to “Flow average”.
• Set the UNITS_INDEX parameter to the desired flow units i.e. “L/s”.
• Set the L_TYPE parameter to “Indirect” It can also be ‘Direct’ if XD_SCALE and

OUT_SCALE parameters have the same values.

Confirm that the BLOCK_ERR parameter indicating ‘Out of Service’. Once all of the

above have been confirmed, set the block Mode into AUTO, and confirm that the

bock is providing updated flow process data in the OUT parameter. If all conditions

are met then the MODE_BLK.ACTUAL parameter of AI block goes into ‘Auto’.

Configuring the Temperature AI Block
The configuration process is similar to the Flow AI block except for the parameter setting below.
• Set the CHANNEL parameter to “Temperature average”.
• Set the UNITS_INDEX parameter to the desired temperature units i.e. “°C”.