Resource block – Fluid Components International ST100 Series Foundation Fieldbus User Manual

Page 9

Advertising
background image

ST100 Series Foundation Fieldbus

Fluid Components International LLC

7

DS-85

Test Structure

Other Data Types used in the ST100
• Unsigned 16 and 32 bit integers
• Floating Point (Single Precision)

Resource Block
This block contains data that is specific to the ST100 hardware that is associated with the resource. All data is modeled as contained,

so there are no links in the Block.

ITK_VER parameter
This parameter informs to which ITK version is this device certified to. The ST100 is certified to Version 5.

FD_VER parameter
This parameter informs which Field Diagnostic Specification was used in the development of the device. The ST100 used

Version 1.

MANUFAC_ID parameter
This parameter provides the manufacturer identification number. An interface device to locate the DD file uses the MANUFAC_

ID parameter. The manufacturer ID for Fluid Component international is 0x01FC49.

DEV_TYPE parameter
This parameter informs of the manufacture’s number associated with the resource. The Fluid Components model number is FCI

ST100.