E (semi-automatic): This mode requires a
command to open and a command to close. A

second command during opening stops the

gate. A second command during closing

reopens the gate.

EP (semi-automatic, step by step): This mode
requires a command to open and a command to

close. A second command during opening or

closing causes the gate to stop. A third

command then reverses the previous motion of

the gate.

B (manned, pulsed): This mode is designed for
guard station use and requires a three-button

switch (pulsed) to open, close, and stop the

gate.

C (manned and constant): This mode requires
constant pressure switches. One to open and

one to close. No pressure on a switch stops the

gate.

The three programming push buttons allow the

programming of the torque (or pressure), the pause

time between opening and closing, and the leaf delay on

closing.

WARNING! Turn the main power off before you
make any electrical connections.

For all FAAC hydraulic operators using the 455 D

control panel, the force must be set at its maximum
setting of 50 in order to supply the correct voltage to

the operator.

P

AUSE

T

IME

:

The pause time between opening and

closing can be adjusted from 0 seconds to 4 minutes.

Time is adjusted in one-second increments from 0—59

seconds. When 60 seconds is reached, time is adjusted

in 10 second increments up to 4 minutes. i.e. if display

shows 2.5, it means 2 minutes and 50 seconds.

L

EAF

D

ELAY

:

You may choose to delay one leaf on

closing for overlapping gate leaves. Be sure the operator

on the leaf for delayed closing is connected to Motor 1.

On opening, the leaf connected to Motor 2 is delayed

2.5 sec.

N

OTE

: If an opening leaf delay is desired, it must be

enabled in the Advance Programming. However, if

enabled, you cannot adjust this opening delay of

the operator connected to Motor 2.

The closing leaf-delay time is adjustable from 0 to 4

minutes.

N

OTE

: If the opening/closing time is set at less

than the leaf delay time, the delayed leaf closes at

the end of the closing time.

Page 6

November, 2003

455 D Control Panel Installation Instructions

opening and closing, respectively, are triggered. Use

the LEDs and the next table to determine if the

accessory devices you have installed are operating

properly.

Electric Locks: An electric lock can be wired to the 455
D in terminals 18 and 21 (12Vac pulsed provided). If a

reversing stroke is needed to allow the electric lock to

release, this must be done in advanced programming.

See page 7 for the connections for a magnetic locking

device.

W

ARNING

L

IGHT

: Connect a warning light to

terminals 18 and 20 in the group labeled W.LIGHT

in terminal block J1 and J5. The terminals provide

an output voltage of 24 VDC, maximum power 3

Watts. This output voltage will power most 24 VDC

warning lights.

N

OTE

: The behavior of the warning light varies

according to the logic you have set.

L

OGICS

A, S, E, EP,

AND

B: The warning light is on

steadily during opening and the pause phase. During

closing, the light flashes.

L

OGIC

C: The warning light is on steadily during opening

and flashes during closing.

S

ET

O

THER

O

PERATING

C

ONTROLS

WARNING! Turn the main power off before you
make any electrical connections.

You need to program the control panel for your gate's

operation. The 455 D Control Panel has on board

programming that controls a wide range of functions.

O

PERATING

L

OGICS

N

OTE

: The 455 provides inputs for opening

reversing devices and closing reversing devices.

FAAC strongly recommends the use of

reversing devices, such as photocells or other

non-contact sensors.

A (automatic): The gate opens on command
and automatically closes after a pause phase. A

second command while opening is ignored; a

second command during the pause phase

interrupts the pause time; a second command

during closing reopens the gate. A maintained

open command will hold the gate open.

S (security): The security mode is like A logic
except that a second command during opening

immediately closes the gate. A maintained

open command will not hold the gate open.