ADIC Scalar Series User Manual

Page 54

Advertising
background image

44

Operation and Maintenance

Note

To initiate the cleaning cycle manually you must be aware of the
present state of the Scalar Library and the drive that you wish to clean.

If a cartridge is present in the drive, you must first press the UNLOAD
button on the drive front panel, then, when the OPERATE HANDLE
LED is illuminated, open the drive door and remove the cartridge. You
can then proceed with these instructions.

If the drive is empty, but the door is closed, make sure that the
OPERATE HANDLE LED is illuminated before opening the door.
You may then proceed with these instructions.

If the drive is empty, and the door is open, proceed with these
instructions.

p Open the front door of the Scalar Library.

Note

You can manually move the Media Picker assembly right or left to
provide access to the drives. Avoid manually moving the Media Picker
assembly up or down.

p Insert the cleaning cartridge into the drive you wish to clean. Close the drive door handle.

The cleaning cycle will be performed. When cleaning is completed, the drive will unload the cleaning cartridge.
Remove the cleaning cartridge and check a usage box on the label.

p To resume normal operation, close the door and lock it.

Causes of the Use Cleaning Tape Warning

The most common reasons that the Use Cleaning Tape LED gets turned on for, in order of highest rate of
occurrence, are listed below:

Dirty ("Stained") heads.

A cleaning cycle must be executed to clear this indication.

Worn tape.

DLT tapes are rated at 500,000 passes. Applications that overwrite small blocks of data cause "shoe shining"
of the tape against the head and will reach the 500,000 passes sooner than might be expected.

Bad environment.

Data errors result from a number of factors, each of which subtract from the margin between good data
recovery and an error. High levels of dust contamination, high humidity, and heat can be significant
factors.

Advertising