Part 1 Installation

List of Motor Drive Powers

Power

[W]

(rated output)

Power

y 0.6

[Power factor] [VA

Output stage loss

[W]

NN

…2515

NN

…3515

TNN3015
TNN3515

UNN3015
UNN3515

615.8 1026.3 24.75

NN

…50……

NN

…60……

HNN5020
HNN6020

INN5020
INN6020

1122.8 1871.3 44.12

NN

…70……

NN

…80……

HNN7020
HNN8020

INN7020
INN8020

2120.4 3534.0 78.41

SCARA (Conventional models)

NSN5016H
NSN6016H

2003.7 3339.5 72.21

20W 15.6 26.0 1.58
30W 27.6 46.0 2.07
60W 83.0 138.3 3.39

100W 140.1 233.5 6.12
150W 196.9 328.2 8.30
200W 252.6 421.0 9.12
400W 477.5 795.8 19.76
600W 698.2 1163.7 27.20

Linea

r mo

ve

ment axi

s

750W 912.8 1521.3 29.77

The power values in the table include the motor drive power, copper loss and driver output loss.

[1] Motor power source capacity

The power source capacity of the motor power supply is obtained as the total sum of all powers for
the number of actuators used, based on the applicable values shown in the table.

[2] Heat output of the motor power supply

The heat output from the controller’s motor power supply is obtained as the total sum of all output
stage losses for the number of actuators used, based on the applicable values shown in the table.

Motor power source capacity [VA] = (Power of each axis

y 0.6 [Power factor])

Heat output from motor power supply [W] = (Output stage loss of each axis)