Part 1 Installation

[9] Emergency stop (in combination with drive-source cutoff reset input)

x I/O parameter No. 24, bits 0 to 3 = 0: The RDYOUT output (system I/O) is SYSRDY (PIO trigger

program operation enabled) and the hardware is normal
(emergency stop is not actuated and no hardware errors are
detected).

x I/O parameter No. 44 = 0:

The drive-source cutoff reset input is not yet used.

x I/O parameter No. 47 = 3:

Output function 301 = READY output (PIO program operation
enabled and no errors of cold start level or higher have
occurred).

200-VAC control power

Normal CPU start

I/O input signal: Port No. 14
Drive-source cutoff reset input

I/O output signal: Port No. 301
Ready output

Rdy (system I/O)

SDN (system I/O)

EMG1, EMG2 (system I/O)

ENB1, ENB2 (system I/O)

Emergency stop SW = ON Emergency stop SW = OFF