IDEC SG4 Type 4 Finger & Hand User Manual

Page 32

Advertising
background image

SG4-B Series

Instruction Manual

28

4.1. Notes on connections

For the correct functioning of the SG4 safety light curtains, the
following precautions regarding the electrical connections have to be
respected:

 Do not place connection cables in contact with or near high-voltage

cables and/or cable undergoing high current variations (e.g. motor
power supplies, inverters, etc.);


 Do not connect in the same multi-pole cable the OSSD wires of

different light curtains;


 The TEST wire must be connected through a N.O. button to the

supply voltage of the ESPE.


 The RESET/RESTART wire must be connected through a N.O.

button to the supply voltage of the ESPE.


The TEST button must be located in such a way that the operator
can check the protected area during any test (see section 6
Functioning mode”).

The RESET/RESTART button must be located in such a way that the
operator can check the protected area during any reset operation
(see section 6 “Functioning mode”).

 The device is already equipped with internal overvoltage and

overcurrent suppression devices. The use of other external
components is not recommended.