5 4-point inputs/4-point relay – Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 20
20
15.5 4-point inputs/4-point relay-output module,16-point inputs/8-point relay-
output module
RELAY OUTPUTS WELDED CLOSED
• Always protect relay outputs from inductive alternating current load damage using an
appropriate external protective circuit or device.
• Do not connect relay outputs to capacitive loads.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EXM-DMM8DRT
EXM-DMM24DRF
Rated Input Voltage
24 VDC
Rated Input Voltage Range
DC20.4 to 28.8 V
Rated Input Current
7.3 mA/input (when 24
VDC is applied)
7 mA/input (when 24
VDC is applied)
No. of Input Points
4 points (sink/source
type - dual use)
16 points (sink/source
type - dual use)
No. of Input Common
1
Input ON Voltage
15 VDC or higher
*1
Input OFF Voltage
5 VDC or less
Input Impedance
3.3 k
Ω
3.4 k
Ω
Isolation Method
Between input terminals and internal circuit:
photocoupler isolated
Between input terminals: not isolated
Input Delay
OFF-ON
4 ms
ON-OFF
4 ms
Usage Limits
No limits
Limits
*2
External Load for I/O
Interconnection
Not needed
Signal Determination Method
LED lights when each point turns ON (logical side)
No. of Output Points
4 points (4 points/1
common)
8 points
No. of Output Common
1 NO
2 NO
Output Method
1a-contact
Maximum Load
Current
*3
Per Channel
2 A or less
Per Common
7 A or less
Min. Open/Close Load
0.1 mA/0.1 VDC (reference value)