is in the specified input range. Before inputting the value, therefore, consider the maximum error.

*1 Compatible with models that have revision “PV: 03 RL: 07 SV: 1.2”. Please refer to “Revision” on page 5.
*2 Compatible with models that have revision “PV: 04 RL: 08 SV: 2.0”. Please refer to “Revision” on page 5.
*3 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value

between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum
values can be selected using data registers allocated to analog I/O modules.

EXM-AMM3HT

Analog Output Specifications

Voltage Output

Current Output

Rated Output Voltage Range

From DC0 to 10 V

From DC4 to 20 mA

Load

Load Impedance

2 k

Ω min.

*1

, 1 k

Ω min.

*2

300

Ω max.

Application Load Type

Resistive load

D-A
Conversion

Conversion Time

50 ms

*1

10 ms

*2

Total Output System
Transfer Time

50 ms + 1 scan time

*1

10 ms + 1 scan time

*2

Output
Error

Maximum Error at 25°C (77°F) ±0.2% of full scale
Temperature Coefficient

±0.015% of full scale/°C

Repeatable after
Stabilization Time

±0.5% of full scale

Output Voltage Drop

±1% of full scale

-

Nonlinear

±0.2% of full scale

Output Ripple

1 LSB max.

Overshoot

0%

Total Error

±1% of full scale

Data

Digital Resolution

4,096 increments (12 bits)

Output Value of LSB

2.5 mV

4 µA

Data Type in Application
Program

0 to 4095 (12 bit data)
-32768 to 32767 (optional range designation)

*3

Monotonicity

Yes

Current Loop Open

-

Not detectable

Noise
Resistance

Maximum Temporary
Deviation during Electrical
Noise Tests

±3% maximum

*1

or ±1% maximum

*2

when a

1 kV clamp voltage is applied to the I/O wiring
and 1 kV is applied to the power directly.

Cable

Twisted-pair shielded cable is
recommended for improved noise immunity

Crosstalk

No crosstalk because of 1 channel output

Voltage Endurance

500 V between output and power circuit

Isolation Method

Photocoupler Isolation between output and
internal circuit

Selection of Analog Output Signal Type

Using software programming

Calibration or Verification to Maintain
Rated Accuracy

Approximately 10 years

Disconnection detection

No