Wiring, Wire cabling: 3-wire cabling: 4-wire cabling – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 45

Advertising
background image

45

‹ Wiring

indicates a fuse.

• The power for the analog module

should be supplied separately from
the LT.
Turn the analog module on before
turning the LT on. Wait at least 30
seconds after power-off to restart the
external power-supply or it may not
operate properly.

• Be sure the analog IN/OUT lines

(especially, Temperature Probes) are
placed in a separate duct from high-
frequency, live lines such as high-
voltage, high-power lines, inverters,
etc.

• Connect a fuse appropriate for the

applied voltage and current draw, at the
position shown in the diagram.

• Do not connect cables to a channel that is

not used. When the input is open, an
error code (RGEF130 input data error)
occurs to the unused channels, then the
invalid values are input. Do not map the
parameters on the unused channels.

• When connecting an RTD, connect the

three wires to terminals A, B', and B of
input channel 0 or 1.

• When connecting a thermocouple,

connect the two wires to terminals B' and
B of input channel 0 or 1.

- +

+

-

B’

B

+

-

A

+

-

OUT

IN0

+

-

NC

+

-

IN1

NC

+

-

A

B’

B

A

B’

B

- +

+

-

B’

B

+

-

A

+

-

OUT

IN0

+

-

NC

+

-

IN1

NC

+

-

A

B’

B

A

B’

B

- +

+

-

B’

B

+

-

A

A’

+

-

OUT

IN0

+

-

NC

+

-

IN1

NC

+

-

A

B’

B

A

B’

B

*1

*1 For 4-wire cabling, output A' is not connected.

2-wire cabling:

3-wire cabling:

4-wire cabling:

Analog voltage/
current input
device

RTD

24 VDC

24
VDC

Thermocouple

Analog voltage/
current input
device

RTD

24 VDC

24
VDC

Thermocouple

Analog voltage/
current input
device

RTD

24 VDC

24
VDC

Thermocouple

Shield

Shield

Shield

<EXM-ALM3LT>

Advertising