Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 40

Advertising
background image

40

*1 Total input system transfer time = sample repetition × active channel number + 1 scan time.
*2 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value

between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum

values can be selected using data registers allocated to analog I/O modules.

*3 If the input data is not in the range, the error code RGEF130 (Input data error) is output for the analog

module. Once the error occurs, input data from the point of the error is no longer updated. For more

information about error codes, read the “Maintenance/Troubleshooting Guide”.

*4 The input value may be regarded as "Input Data Out of Range" due to the maximum error even when it

is in the specified input range. Before inputting the value, therefore, consider the maximum error.

*1 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value

between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum
values can be selected using data registers allocated to analog I/O modules.

EXM-AMM6HT

Analog Output Specifications

Voltage Output

Current Output

Rated Output Voltage Range

DC0 to 10 V

From DC4 to 20 mA

Load

Load Impedance

2 k

Ω min.

300

Ω max.

Application Load Type

Resistive load

D-A
Conversion

Conversion Time

20 ms

Total Ouput System
Transfer Time*

1

20 ms + 1 scan time

Ouput Error

Maximum Error at 25°C
(77°F)

±0.9% of full scale

Temperature Coefficient

±0.015% of full scale/°C

Repeatable after
Stabilization Time

±1% of full scale

Output voltage drop

±1% of full scale

Nonlinear

±0.5% of full scale

Output Ripple

±0.5% of full scale

Overshoot

±0.5% of full scale

Total Error

±1.5% of full scale

Data

Digital Resolution

4096 increments (12 bits)

Output Value of LSB

2.5 mV

4.8 µA

Data Type in Application
Program

0 to 4095 (12 bit data)
Custom range up to -32768 to +32767*

1

Noise
Resistance

Maximum Temporary
Deviation during Electrical
Noise Tests

±1% of full scale

Cable

Twisted-pair shielded cable is
recommended for improved noise
immunity

Crosstalk

±0.1% of full scale max.

Voltage Endurance

800 VAC

Isolation Method

Photocoupler Isolation between outputs
and internal circuit

Selection of Analog Input Signal Type

Using software programming

Calibration or Verification to Maintain
Rated Accuracy

Approximately 10 years

External Connection

10-pin terminal connector

Advertising