PS-3650A / PS-3651A Reference Manual

3-6

‹ External Input Signals

The PS-A’s RAS interface connector uses the following input signals.

General-Purpose Input (DIN 2 bits)

This standard digital input is used for error/alert detection in external devices. The input signal uses two bits.

The System Monitor property of the control panel or the API-DLL can be used to enable or disable this

feature, as well as designate what type of processing is to be performed once a signal is received. (Only

the “ON” state of the DIN circuit is detected. The “OFF” state of the DIN circuit cannot be monitored.)

Remote Reset Input

This is the reset signal sent from an external device to the PS-A. When this signal is enabled, a forced

reset of the PS-A is performed.

The System Monitor property of the control panel or the API-DLL can be used to enable or disable this

feature.

To enable Remote Reset Input, make sure to check the [Enable] in the Remote reset tab of

System Monitor Property. For Remote reset of System Monitor Property, refer to the following.

Input Voltage

DC12V to 24V

Input Method

Sink / Source Input

Input Current

10mA ( DC24V )

Input Resistance

3.6k

Input Points

2 points (common with external reset input)

Operation Range

ON voltage

DC10V or more

OFF voltage

DC3V or less

Isolation Method

Photocoupler Isolation

Dielectric Strength Voltage

500V or more

SEE

3.8.5 Remote reset (page3-33)

(Interface Circuit)

+5V

1.8k

1/10W

1.8k

1/10W

R

R

PC357

No polarity - for Sink /
Source input

switch or other
switching device

Cable

DC12V
to 24V

DINCOM pin # 9

DIN0(+) pin

#

4

DIN1(+) pin

#

5