PS-3650A / PS-3651A Reference Manual

4-4

The touch position recognized in
the touch panel still deviates
from the actual touch even after
calibration.

If the touch position still deviates after calibration,
possible causes are:
• There are flaws or unevenness on the surface of the

PS-A.

Æ If the bracket securing the PS-A is tightened too much,

flaws or unevenness may result. Release the PS-A
from the bracket and check whether the problem
continues.

• The touch panel calibration was not finished properly.
Æ Uninstall the touch panel driver once, and then install

the latest driver. The latest driver can be downloaded
from the Pro-face support site “Otasuke Pro!”.

• The hardware in the touch recognition section is faulty.
Æ Use the PS-A that operates properly and check

whether the same problem occurs. If the problem
occurs only with a specific unit, contact your local PS-A
distributor for repair or replacement.

I want to know what the LED
indicator indicates.

A Touch Panel Self-Test Error
occurred.

The touch panel is faulty. Please contact your local PS-A
distributor.

A “Smart Alert” occurred

Predicts the malfunction and life expectancy of the hard
disk. It is recommended that the disk be replaced before
experiencing malfunction or reaching the end of its life.

Problem

Countermeasure and reference page

SEE

‹

LED Indicator (page3-5)