11

<Compliance and Handling Cautions in Hazardous Locations>

Suitable for use in Class I, Division 2, Groups A, B, C, and D Hazardous Locations only.

WARNING: Explosion hazard - substitution of components may impair suitability for Class I, Division 2.

WARNING: Explosion hazard - do not disconnect equipment while the circuit is live or unless the area is known to be

free of ignitable concentrations.

<Control Drawing of USB I/F on FP's Front Module>

The information below concerns the use of the USB I/F located on the FP unit's front modules used in Class I,

Division 2 Groups A, B, C, and D hazardous locations (from Doc No. 35016429).

FP's Front Module

Notes:

(1)

Nonincendive Circuit Parameters:

Front USB I/F:

Voc = 5.0 V, Isc = 1.25 A, Ca = 10 mF, La = 16 mH

(2)

Selected Associated Nonincendive Field Wiring Apparatus shall satisfy the following:

(3)

If the electrical parameters of the cable are unknown, the following values may be used:

Capacitance = 60pF/ft, Inductive = 0.20 µH/ft

(4)

Nonincendive Field Wiring must be installed in accordance with article 501.10(B) of the National Elec-

trical Code ANSI/NFPA 70.

(5)

Nonincendive Field Wiring Apparatus shall not contain or be connected to another source of power.

The safety certificate can be downloaded from Pro-face Home Page.
Home Page URL
http://www.pro-face.com/

Nonincendive Field
Wiring Apparatus

-

Front module of FP unit

Voc

Vmax

Isc

Imax

Ca

Ci+C cable

La

Li+L cable

USB Pin Description

(See note 1 for detail)
Shield. Gnd

1.Vcc

2.D-

3.D+

4.GND

1

2

3

4

Nonincendive Field

Wiring Apparatus