Chapter 5 Installation and Wiring

5-7

5.2

Wiring

5.2.1

Connecting the Power Cord

„FP-3710K Series

‹ Power Cable specification

Use copper conductors only.

To avoid an electric shock, when connecting the FP’s power cord terminals to the power

terminal block, confirm that the FP’s power supply is completely turned OFF, via a breaker,

or similar unit.

To avoid the dangers of fire, electric hazards and equipment damage, be sure to use only

the specified voltage when operating the FP.

Since there is no power switch on the FP unit, be sure to attach a breaker-type switch to its

power cord.

Power Cord Diameter

0.75 mm

2

to 2.5 mm

2

(18 AWG to 12 AWG)

Conductor Type

Simple or Twisted Wire

Conductor Length

• If the Conductor’s end (individual) wires are not twisted correctly, the end wires

may either short against each other, or against an electrode.

10 mm [0.39 in.]