FP-3710K Series User Manual

5-4

Be sure that the ambient operating temperature and the surrounding operating humidity are within their

designated ranges. (When installing the FP in a cabinet or an enclosure, “Ambient operation temperature”

indicates both the panel face and cabinet or enclosure's internal temperature.).

Be sure that heat from surrounding equipment does not cause the FP to exceed its standard operating tem-

perature.

When installing the FP in a slanted panel, the panel face should not incline more than 30

o

.

When installing the FP in a slanted panel, and the panel face inclines more than 30

o

, the ambient tempera-

ture must not exceed 40

o

C. You may need to use forced air cooling (fan, A/C) to ensure the ambient oper-

ating temperature is 40

o

C or below.

Panel Face

Inside of the
enclosure

Unit: mm

[in.]

100
[3.94]

100
[3.94]

30
[1.18]

30
[1.18]

Ambient Operating Temperature: 0 to 50

o

C

Surrounding Operating Humidity:10 to 90%RH

No more than 30 degrees of tilt