App index – Yokogawa Standalone MW100 User Manual

Page 228

Advertising
background image

5-15

IM MW100-01E

Specification

1

2

3

4

5

App

Index

Report Recording Function (/M3 Option)

Record start/stop operation: Executed simultaneously upon recording start/stop of

measured and computed values. No trigger function available.

Report data:

Creates daily, weekly, and monthly data. The creation time for
daily, weekly, and monthly reports is the same as the daily report
file creation time.

Report recording channels:

Can be specified for each channel (up to 60 channels).

Data format:

Tab delimited text

File name:

Automatically generated using the date and serial number (the
date is the file create date)

jyymmddn.DAR

j:

D (daily), W (weekly), M (monthly)

yy: Year when file created (local time), last 2 digits of Western

calendar

mm: Month when file created (local time), 01 to 12

dd: Date when file created (local time), 01 to 31

n:

Serial number (0 to 9, A to Z)

DAR: Report file extension (uppercase)

Maximum file size:

Approximately 135 KB/file (max)

Saving Settings

Saves settings to CF card.
Saving/loading:

Set by user function key on the main unit, browser, or by
communication command. From the user function key, only the
SETTING.PNL file can be saved and loaded.

Settings that can be saved:

All settings are saved

Saved items:

Channel: Input range, output range, expression, calculation

constant, MATH group, alarm, delay alarm, rolling
average, filter and TC, strain input, relay, program
channels, measurement operation, computation
operation, output operation, and tag settings.

Recording: Recording channel, recording operation, thinning

recording operation, save option, file message, and
data save folder settings

Communication: User, serial communication, IP address*, server,

Modbus client 1 to 3, Modbus master 1 and 2,
DNS client, FTP client, mail client 1 to 3, and
time synchronization client settings.

* The DNS and IP address information can be saved,

but the information is not loaded.

Others:

Event action, timer, match time, report, other (system),
Daylight Savings Time, color, graph scale, trip line,
message, display group, and other (display) settings.

File creation location: CONFIG folder on the CF card
Created file name:

From the user function keys, SETTING.PNL.

An arbitrary file name can be set with the PNL extension from
communication commands or the browser. The maximum number
of characters for the file name is 8 excluding the extension.

5.2 Main Module (MW100-E) Specifications