Input Registers

Data

Data Type

33001

Lower byte of computed data of computation channel A001

Int 32

33002h

Upper byte of computed data of computation channel A001

|

|

33599

Lower byte of computed data of computation channel A300

33600

Upper byte of computed data of computation channel A300

.• No decimal place information

34001

Lower byte of computed data of computation channel A001

Float

34002

Upper byte of computed data of computation channel A001

|
34599

Lower byte of computed data of computation channel A300

34600

Upper byte of computed data of computation channel A300

• Includes decimal place information.

35001

Alarm status of computed data of computation channel A001

Bit string

|

|

35300

Alarm status of computed data of computation channel A300

• Register structure and alarm status value: Same as alarm status of measured data.

36001

Data from measurement channel 001

Int 16

36002

Data from measurement channel 002

|

|

36060

Data from measurement channel 060

• No decimal place information
• Firmware version R3.04or later

37001

Data from MATH channel A001

Int 16

37002

Data from MATH channel A002

|

|

37300

Data from MATH channel A003

• No decimal place information.
• Firmware version R3.04 or later

38001

Measuring

Int 16

38002

Computing

Int 16

38003

Recording

Int 16

38004

Alarm occurring

Int 16

38005

Waiting to confirm alarm status

Int 16

• Input registers indicating mode information are 1 (On) during operation in the relevant

mode, and 0 (Off) when stopped.
• Firmware version R3.03 or later

39001

Year

Int 16

39002

Month

39004

Hours

39005

Minute

39006

Second

39007

Milliseconds

39008

DST(0, 1)

Hold Registers

Data

Data Type

40001

Lower byte of communication input channel C001

Float

40002

Upper byte of communication input channel C001

|

|

40599

Lower byte of communication input channel C300

40600

Upper byte of communication input channel C300

41001

Lower byte of communication input channel C001

Int 32

41002

Upper byte of communication input channel C002

|

|

41599

Lower byte of communication input channel C300

41600

Upper byte of communication input channel C300

• Firmware version R3.04 or later

42001

Communication input channel C001

Int 16

42002

Communication input channel C002

|

|

42300

Communication input channel C300

• Firmware version R3.04 or later

5.2 Main Module (MW100-E) Specifications