Condec UPS3210 User Manual

Page 16

Advertising
background image

12

UPS3000/UPS3110/UPS3210 Operation & Maintenance Manual

2.6

Engineering Conversion with PEAK HOLD or MAX/MIN Option

See Figure 2-7 on page 8 for location of “Data Enter” and rocker switches.

NOTE: When the PEAK HOLD or MAX/MIN option is supplied with a model having the ABS/GAGE mode, switch
selectable from front panel, the
CONV button will be disabled and will not be present on the front panel.

Figure 2-9. Peak Hold Option Front Panel Switches

Figure 2-10. MIN/MAX Option Front Panel Switches

In order to step the light bar on conversion display to required conversion the following steps must be taken:

1. Open UPS3000/UPS3110/UPS3210 per Section 4.2.1 on page 28.

2. At this time, record the settings of rocker switches S1 and S3. These settings must be changed in order to

program the new conversion configuration.

3. Close the following rocker switches S1 position 3 and S3 positions 1 and 3.

4. Verify Numeric display has “

1 XXX

”, where X’s are some random number.

NOTE: If 1 is not on display open rocker switch S1 position 3 and rocker switch S3 positions 1 and 3, then restart at step
3 above.

5. Push the

ABS/GAGE

switch located on front panel as needed to move light bar on conversion display to

required conversion.

6. Momentarily push the “

Data Enter

” switch S2 to enter new conversion.

7. Open the following rocker switches S1 position 3 and S3 positions 1 and 3.

NOTE: Verify rocker switches S1 and S3 conform to original settings which had been recorded earlier.

8. To verify proper conversion is active remove and restore power to the UPS3000/UPS3110/UPS3210.

Advertising
This manual is related to the following products: