RT‐10 Flow Monitor

 

Operation and Programming Manual 

 

 

 

17 

      
 

Max. Gate Time vs Frequency

0

100

200

300

400

500

600

700

0

500

1000

1500

2000

2500

3000

Hz

Se

c

o

n

d

s

 

D ISPLA YS
B RIEFLY

EN TER TIM E IN SEC ,
FO R UPD A TE O F
D ISPLA Y A N D

A N A LO G.

GA TE TIM E (UPD A TE) FO R RA TE

TIM E B A SE FO R RA TE

EN T

EN T

EN T

SEL

EN T

HO LD
3 SEC .

H O LD EN T

1 SEC

1 SEC

EN T

SEL

SEL

SEL

TO TO TA L

D ISPLA Y

M O D E

D ISPLA YS
B RIEFLY

1 SEC

M O D E

FRO M C LO C K O R TO TA L D ISPLA Y

value is 3 seconds. The maximum allowable Gate time depends on the expected maximum input 
frequency and is determined by the formula: 

Maximum gate time (seconds) = 65,535 counts/maximum frequency in Hz 

To calculate the maximum frequency, use the formula: 

Maximum flow rate (engineering unit/sec) X K‐factor (pulses/engineering unit) = frequency in Hz 

The maximum gate time value versus frequency is represented in the following graph. 

 

 

 

 

 

 

When editing the Gate Time variable, the leftmost digit will blink (cursor). Use SEL to move the cursor to 
the right; the cursor wraps around. Use UP or DN to increment or decrement numerals. Edit the decimal 
point last. Use DN to move the decimal point to the right, UP to move it to the left. When the desired 
value displays, use ENT to store the value and exit or advance to the next variable.  

 

 

Advertising