Rt‐10 flow monitor, Clock mode programming – AW Gear Meters RT-10 User Manual

Page 21

Advertising
background image

RT‐10 Flow Monitor

 

Operation and Programming Manual 

 

 

 

20 

      
 

Clock Mode Programming

 

Use the Clock Display Mode to set the time on the real‐time clock (if necessary), and to program the 
“Sleep Time.” The Sleep Time determines the length of the period of inactivity (no pulse or switch 
activity) before the RT‐Ex10 “sleeps” to conserve energy. 

Setting the Time 

To view the Clock Display Mode, use the DN/MODE button or magnetic switch. Press and hold the ENT 
button or activate, and maintain the ENT magnetic switch, for 3 seconds until the display (briefly) 
indicates “tinE‐P” (time programming) followed by the current hour (HH:   :    ), which blinks. Use UP/DN 
to set the hours and then ENT to continue.  

The current minutes (HH:MM:    ) become visible and blink. Use UP/DN to set the minutes and then ENT 
to continue.  

 

Seconds begin at zero the instant you press ENT. 

Sleep Timer 

The display (briefly) indicates “SLEEPt” (Sleep Time) followed by the current Sleep Time value. Program 
the Sleep Time in minutes; default value is 5 minutes. The minimum value allowed is 2 minutes and the 
maximum 254 minutes. If you enter a value less than 2 or greater than 254, the display reverts to the 
mininimum or maximum value. When you edit Sleep Time, the leftmost digit blinks (cursor). Use SEL to 
move the cursor to the right. The cursor wraps around. Use UP or DN to increment or decrement 
numerals. Edit the decimal point last. Use DN to move the decimal point to the right, UP to move it to 
the left. When the desired value appears, use ENT to store the value and exit Clock programming. 

 

 

Notice 

EN T

HO LD EN T

H O LD

3 SEC .

1 SEC

EN T

EN T

1 SEC

M O D E

TO
RA TE

D ISPLA Y

SETTIN G THE TIM E

SLEEP TIM ER

USE UP/D O W N TO
SET M IN UTES.

W HEN M IN UTES A RE

SET PRESS EN T TO
STA RT C LO C K A T
ZERO SEC .

USE UP/D OW N TO
SET H O URS. PRESS
EN T W H EN D O N E.

EN TER TIM E IN M IN .
FO R SLEEP A FTER
IN A C TIVITY. (2 M IN .
IS M IN IM UM ).

1 SEC

D ISPLA YS
B RIEFLY

D ISPLA YS
B RIEFLY

D ISPLA YS
B RIEFLY

M O D E

FRO M TO TA L D ISPLA Y

Advertising