Analog Scaling (option) 

 

Will not display if model does not include analog output. 

The display (briefly) shows ANALOG followed by the currently programmed Analog Scaling value. This 
scaling variable is used to set the maximum output of 20 mA to a corresponding rate value, which  
produces an output ranging from 4 mA for a zero value to 20 mA for the programmed flow rate. The 
default initial value is 50.000 (Hz by default K‐factor). Enter the variable directly in the engineering units 
dictated by the K‐factor and Rate Time Base.  

Example:  

 K‐factor entered in pulses per gallon 
 Time base programmed for 60 Sec 
 Enter 20.000 for 20mA = 20 GPM 

When editing the Analog Scaling variable, the leftmost digit will blink (cursor). Use SEL to move the 
cursor to the right; the cursor wraps around. Use UP/DN to increment or decrement numerals. Edit the 
decimal point last. Use DN to move the decimal point to the right, UP to move it to the left. When the 
value displays, use ENT to store the value, exit programming, and return to the RATE display. 

M O D E

1 SEC

D ISPLA YS
B RIEFLY

M O D E

TO TO TA L

D ISPLA Y

SEL

SEL

SEL

EN T

1 SEC

1 SEC

1 SEC

EN T

HOLD EN T

HO LD
3 SEC .

EN T

SEL

EN T

EN T

EN T

TIM E B A SE FO R RA TE

GA TE TIM E (UPD A TE) FO R RA TE

A N A LO G SC A LIN G

EN TER TIM E IN SEC ,
FO R UPD A TE O F
D ISPLA Y A N D

A N A LO G.

EN TER RA TE IN
E- UN ITS PER TIM E
B A SE FO R 2 0 m A
O UTPUT

D ISPLA YS
B RIEFLY

D ISPLA YS
B RIEFLY

FRO M C LO C K O R TO TA L D ISPLA Y