RT‐10 Flow Monitor

 

Operation and Programming Manual 

 

 

 

      
 

Specifications

 

Flow Meter Compatibility: positive displacement: JV and HPM series (except JV‐01, JV‐10, and 

JV‐12); turbine: TR, TRG, and TA Series (linear flow range may vary) 

Power: internal 3.6V “C” cell battery, field replaceable; four year battery power estimated 

average life, depending on RT‐10 model 

Sensor/Monitor Frequency Range: 0‐3,000 Hz 
Fiber‐Optic Frequency Output (Option): 0‐100 Hz programmable scaling 
Temperature Rating: ‐20° to 70°C (‐4° to 158°F) ambient; 80°C (175°F) maximum fluid 

temperature 

2‐Wire Loop Powered 4‐20 mA Output (Option): loop power = 12‐24 Vdc ±10%; max. load = 250 

Ohm @ 12V, 500 Ohm @ 24V    

Enclosure Certification:  NEMA 4X 

Customer Connections 

Two types of connections are available, depending on your need and the model you choose. 

Loop‐Powered Analog Output (loop‐powered analog output models only)  

A two‐wire loop powered 4‐20 mA output option with an analog Rate output has 16‐bit resolution. 
Supply voltage is between 12 and 24VDC, with maximum loads from 250Ω at 12VDC to 500Ω at 24VDC.  

The RT‐10 utilizes the AD421 output device manufactured by Analog Devices. The minimum output is 
trimmed to 4.00mA by the device manufacturer. Consult the manufacturer’s data sheet for complete 
specifications regarding offset tolerance.  

Program the scaling value for the mA output from the Rate display screen. (See ANALOG Scaling on page 
18 for instructions on scaling of the analog output.) 

Wiring for the loop powered output option is via pig‐tail leads with a 3/4" NPT wire exit for conduit 
connection. See illustration next page. 

 

Connection to conduit is required to maintain the enclosure’s hazardous location rating. Make all 
connections in accordance with local and national electrical codes.  

 

Make certain circuits are not live while wiring the RT‐10 in a hazardous area. Keep cover tightly closed 
while circuits are alive.  