3 controls and indicators – Fire-Lite MS-2410BC Conventional Control Panel User Manual

Page 12

Advertising
background image

Controls and Indicators

12

Document #50801 Rev.C 12/14/01 P/N 50801:C

Nonresettable 24 VDC Power - TB2 Terminals 1(-) & 2(+)

Maximum ripple voltage: 10 mV

RMS

Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

1

Recommended maximum Standby current is 150 mA

Refer to Fire•Lite Device Compatibility Chart for compatible listed devices

Remote Trouble Buzzer - TB5

Operating Voltage: nominal 24 VDC

DC current when RTB Remote Trouble Buzzer is in normal standby (AC Power LED on alone) is 20 mA.

Maximum DC current from this output when RTB Remote Trouble Buzzer is active is 50 mA.

1.3

Controls and Indicators

Front Panel Membrane Keys in Normal Mode

Acknowledge

Signal Silence

Drill

Disable/Enable

Reset/Lamp Test

Note that programming keys function slide-in-labels and
option/feature slide-in labels are also provided and should
be inserted while in Program Mode to view the altered key
functions. Refer to Figure 3-1, “Programming Mode Key-
pad,” on page 32 and “Slide-in Labels” on page 57.

LEDs

AC Power - green LED

Alarm - red LED

Trouble - yellow LED

Supervisory - yellow LED

Signal Silence - yellow LED

NAC Fault - yellow LED

Ground Fault - yellow LED

Battery Trouble - yellow LED

Zone Disabled - yellow LED

Annunciator Trouble - yellow LED

Zone Fire Alarm - Zones 1 through 10 - red LEDs

Zone Supervisory Alarm - Zones 9 and 10 only - red LEDs (yellow LEDs for Canadian program option)

Zone Trouble - Zones 1 through 10 - yellow LEDs

Note: A blank slide-in label is provided for circuits 1 through 10 which may be customized by the customer. In
addition, slide-in-labels listing the programming features/options and programming key functions are provided and
should be inserted while in Program Mode.

1. Total current for nonresettable power, four-wire smoke power, and two Notification Appliance Circuits must not exceed 6.0

amps.

Total system current in excess of 3.6 amps requires the XRM-24 Transformer and 12 Amp Hour or 18 Amp Hour

batteries.

FIGURE 1-3:

LEDs and Keypad