Document #50801 Rev. C 12/14/01 P/N 50801:C

39

Program Features and Options

14.

Press the Down arrow key to position the 'cursor' at the Zone 5 trouble LED which corresponds to the Cana-

dian Supervisory option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41

15.

Press the keypad 3 key (Toggle Option) to disable the Canadian Supervisory option. The cursor should blink

at a 1/10 second On and 9/10 second Off rate. The LED will turn off when the cursor is moved off of it

16.

Press the Enter key to store all of the selected options for the Supervisory Alarms feature and move the

pointer to the next feature

3.5

Program Features and Options

3.5.1 Program Features

There are ten features that are programmable through the MS-2410BC keypad. Table 3-2 lists the programming fea-
tures and the alarm zones which represent each feature.

3.5.2 Programming Options

Each programming feature listed in Table 3-2 has two or more options associated with it. This section describes each
feature and the available options.

TABLE 3-2:

Program Feature Indicated by Alarm Zone

Alarm Zone LED Number (red)

Programming Feature

1

Auto-silence

2

Silenceable NACs

3

Walktest (audible/silent)

4

Supervisory Alarms

5

Alarm Verification

6

AC Loss Delay

7

Option Module Supervision

8

Number of Annunciators

9

Trouble Reminder

10

future use

F

O

Annunc. Trouble

Zone Disabled

Battery Trouble

Ground Fault

NAC Fault

Signal Silence

Supervisory

Trouble

Down Arrow

Key

Zone 5

Trouble LED