Battery Calculations

TABLE A-3:

Filtered Load in Alarm

@24 VDC

.

Device Type

# of

Devices

Current

(amps)

Total Current

(amps)

Main Circuit Board

1

X

0.245

=

0.245

1

1. The current shown represents one zone on the Main Circuit Board in alarm. For all ten zones in alarm, the cur-

rent draw increases to 0.590 amps.

RTB Remote Trouble Buzzer

(1 max.)

X

0.050

=

LED-10IM

(1 max.)

X

0.017

=

4XTMF Module

(1 max.)

X

0.011

2

2. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add

another 0.005 amps.

=

4-wire Smoke Detector

3

3. Current limitations of terminals:

TB2, Terminals 1 and 2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mV

RMS

, nonresettable power (100 Hz

ripple if MS-2410BCE)

TB2, Terminals 3 and 4 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mV

RMS

, resettable power (100 Hz rip-

ple if MS-2410BCE)

[ ]

X

[ ]

=

Power Supervision Relay

4

4. Must use compatible listed Power Supervision Relay

[ ]

X

0.025

=

Notification Appliances

5

5. Current limitation of Terminal TB3 circuits is 1.25 amps per Notification Appliance Circuit expandable to 2.5

amps

[ ]

X

[ ]

=

Notification Appliances

[ ]

x

[ ]

=

Current Draw from TB2

3

(alarm

current)

=

Sum Column for Standby Load

6

6. Total current draw listed above cannot exceed:

3.6 amps with standard transformer installed (only)

6.6 amp with both the standard and optional transformers installed

=

amps