Fire-Lite MS-2410BC Conventional Control Panel User Manual

Page 38

Advertising
background image

Programming Function

38

Document #50801 Rev.C 12/14/01 P/N 50801:C

10.

Press the Down arrow key to position the 'cursor' at the Zone 3 trouble LED which corresponds to the Zone 9

Smoke/Supervisory option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41

11.

Press the keypad 3 key (Toggle Option) to select the Supervisory option. The cursor should blink at a 1/10
second On and 9/10 second Off rate. The LED will turn off when the cursor is moved off of it.

Note that in this option, supervisory is either enabled or disabled. If supervisory is disabled, the
smoke option is automatically selected. Since supervisory is enabled, the 'cursor' will blink at a 1/10
second On and 9/10 second Off rate. The LED will turn off when the cursor is moved off of it

12.

Press the Down arrow key to position the 'cursor' at the Zone 4 trouble LED which corresponds to the Zone 10

Smoke/Supervisory option. Refer to Table 3-6, “Supervisory Alarm - Zone 4 Alarm LED,” on page 41

13.

Press the keypad 3 key (Toggle Option) to select the Supervisory option. The cursor should blink at a 1/10

second On and 9/10 second Off rate (refer to step 11). The LED will turn off when the cursor is moved off of
it

F

O

Annunc. Trouble

Zone Disabled

Battery Trouble

Ground Fault

NAC Fault

Signal Silence

Supervisory

Trouble

2410DISP

Down Arrow

Key

Zone 3

Trouble LED

F

O

Annunc. Trouble

Zone Disabled

Battery Trouble

Ground Fault

NAC Fault

Signal Silence

Supervisory

Trouble

Down Arrow

Key

Zone 4

Trouble LED