2 programmable features and options – Fire-Lite MS-2410BC Conventional Control Panel User Manual

Page 33

Advertising
background image

Document #50801 Rev. C 12/14/01 P/N 50801:C

33

Programmable Features and Options

3.2

Programmable Features and Options

Table 3-1 lists the MS-2410BC programmable features and the corresponding options available for each feature. In
programming mode, the zone alarm LEDs are used to 'point' to the program feature and the zone trouble LEDs are
used to select the desired option for each feature.

TABLE 3-1:

Programming Features and Options

Zone Alarm LED

Programmable

Features

Zone Trouble LED

Available Options

1

AUTO-SILENCE

1

Disabled - default

2

Five (5) Minutes

3

Ten (10) Minutes

4

Twenty (20) Minutes

2

SILENCEABLE

NACs

1

NAC 1 & NAC 2 Silenceable (LED On) - default

NAC 1 and NAC 2 Nonsilenceable (LED Off)

3

WALKTEST

1

Audible (LED Off) - default

Silent (LED On)

4

SUPERVISORY

ALARM

1

Zone 9 Latching (LED On) - default

Zone 9 Autoresettable (LED Off)

2

Zone 10 Latching (LED On) - default

Zone 10 Autoresettable (LED Off)

3

Zone 9 Supervisory (LED Off) - default

Zone 9 Smoke Zone (LED On)

4

Zone 10 Supervisory (LED Off) - default

Zone 10 Smoke Zone (LED On)

5

Canadian Supervisory Enabled (LED On) - default

Canadian Supervisory Disabled (LED Off)

5

ALARM

VERIFICATION

1

Verify Alarms (LED On)

Do Not Verify Alarms (LED Off) - default

6

AC LOSS DELAY

1

No Delay - default

2

Six (6) Hour Delay

3

Eight (8) Hour Delay

4

Ten (10) Hour Delay

5

Twelve (12) Hour Delay

6

Fourteen (14) Hour Delay

7

Sixteen (16) Hour Delay

8

Eighteen (18) Hour Delay

7

MODULE

SUPERVISION

1

4XTMF Transmitter Module

2

not used

3

LED-10IM (EIA-485) Module

8

ANNUNCIATOR

MAXIMUM

MONITORED

ADDRESS

1

01 - default

2

02

3

03

4

04

5

05

6

06

7

07

8

08

9

09

10

10

9

TROUBLE

REMINDER

1

Disabled (LED Off) - default

Enabled (LED On)

10

future use