3 lamp test – Fire-Lite MS-2410BC Conventional Control Panel User Manual

Page 52

Advertising
background image

Lamp Test

52

Document #50801 Rev.C 12/14/01 P/N 50801:C

conditions on the FACP have changed since the last panel activation. Table 5-1 lists possible panel activations and
the LEDs which will be on for each in Last Event/History Mode.

To return the control panel to Normal Mode, remove the Security Key from connector J4 on the MS-2410BC main
circuit board. Remove the programming keys function label and reinsert the Normal Mode label C.

The control panel will automatically revert back to Normal Mode after 2 minutes in Last Event/History Mode. If the
Security Key is still installed, the panel keypad will function as expected in Normal Mode. To enter any other mode
of operation, the Security Key must be removed and then reinserted.

5.3

Lamp Test

To perform a Lamp Test, press and hold the Reset/Lamp Test key for more than two seconds. All panel LEDs will
turn on and the piezo sounder will activate.

TABLE 5-1:

History Mode

Latest Panel Activation

LEDs Illuminated

Zone Alarm

Zone Alarm LED & System Alarm LED

Zone Supervisory

Zone Supervisory LED & System Supervisory LED

Zone Trouble

Zone Trouble LED & System Trouble LED

AC Power Loss or Brownout

AC Power LED

Notification Appliance Circuits Silenced by Silence Switch

Signal Silence LED

Ground Fault

Ground Fault LED

Zone Disabled

Zone Trouble LED & Zone Disabled LED

Remote Annunciator Trouble

Annunciator Trouble LED

Notification Appliance Circuit Fault

NAC Fault LED & System Trouble LED

Reverse Polarity Module

System Trouble LED