Battery calculations, Appendix a – Fire-Lite MS-2410BC Conventional Control Panel User Manual

Page 53

Advertising
background image

Document #50801 Rev. C 12/14/01 P/N 50801:C

53

Battery Calculations

Appendix A

Battery Calculations

Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery
calculation.

Note:

1.

7 Ampere Hour battery can be located in the backbox.

2.

Batteries larger than 7 Ampere Hour, up to 18 Ampere Hour, require the BB-17F battery box.

TABLE A-1:

Battery Calculation

Standby Load

Current (amps)

[ ]

X

Required Standby Time in Hours

(24 or 60 Hours)

[ ]

=

_______________

Alarm Load

Current (amps)

[ ]

X

Required Alarm Time in Hours

(i.e. 5 min. = 0.084 hours)

[ ]

=

_______________

Add Standby and Alarm Load for Required Ampere Hour Battery

=

_______________

Multiply by derating factor of 1.2

X 1.2

_______________