Installation of Optional Modules with Remote Accessories

CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.

4XTMF Transmitter Module

Push the disconnect switch to the down position to prevent accidental activation of the municipal box during test-
ing of the control panel. The Disconnect LED will remain illuminated while the municipal box is disconnected.
The System Trouble LED will indicate disconnected and/or open circuit conditions on the municipal box. During
trouble conditions, it is possible to obtain the circuit condition on the alarm reverse polarity output. If this opera-
tion is desired, cut the TBL jumper on the 4XTMF module.

!

Install 4XTMF Module by

plugging into connector

J6

and

J7

on MS-2410BC main board

Disconnect LED

Disconnect Switch

TBL Jumper

1 (+)

2 (-)

3 (+)

4 (-)

5

6 (+)

7 (-)

Remote Alarm (power-limited)*

Remote Trouble (power-limited)*

no connection

Municipal Box (nonpower-limited)*

* Wiring from these terminals can
exit the protected premises.

Cut JP1 for 4XTMF module

placement supervision

Polarities are shown for
module activation

FIGURE 2-17:

4XTMF Module Connections

MS-2410BC Main Circuit Board

4XTMF Module