Wire Requirements

56

Document #50801 Rev.C 12/14/01 P/N 50801:C

Appendix B

Wire Requirements

Connecting external system accessories to the MS-2410BC main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, wire gauge and wire run length per each MS-2410BC
circuit. Reference the chart below to specify wire requirements and limitations for each MS-2410BC.

TABLE B-1:

Wire Requirements

CIRCUIT CONNECTIONS

WIRE REQUIREMENTS

CIRCUIT TYPE

CIRCUIT

FUNCTION

WIRE TYPE AND

LIMITATIONS

RECOMMENDED

MAX. DISTANCE

Feet (meters)

WIRE GUAGE

Initiating Device

Circuit

Connects to

Initiating Devices

Untwisted, unshielded wire

(Do not exceed 100 ohms)

10,000 (3,000 m)

8,000 (2,400 m)

4,875 (1,480 m)

3,225 (975 m)

12 AWG (3.25 mm

2

) Belden 9583

WPW999

14 AWG (2.00 mm

2

) Belden 9581

WPW995

16 AWG (1.30 mm

2

) Belden 9575

WPW991

18 AWG (0.75 mm

2

) Belden 9574

WPW975

EIA-485

LED-10IM Inter-

face Module

Connects to
annunciator

modules and relay

module

Twisted, shielded pair with a

characteristic impedance of

120 ohms

6,000 (1,800 m)

18 AWG (0.75 mm

2

)

24 VDC resettable,

nonresettable

Connects to

annunciators and
other accessories

No more than 1.2 volt drop

allowed from supply source

to end of any branch

Distance limitation

set by 1.2 volt maxi-

mum line drop

12 AWG (3.25 mm

2

) - 18 AWG

(0.75 mm

2

)