Operation

• Turn on supervisory relay

• Blink all remote annunciator general supervisory alarm LEDs (½ second On, ½ second Off)

• Blink all remote annunciator zone supervisory alarm LEDs (½ second On, ½ second Off)

4.3.4 System Supervisory Restoral Response

When the supervisory condition has been cleared and the reset key has been pressed (if zones are programmed for
latching), the control panel will perform the following:

• Turn off the supervisory LED

• Turn off the Zone supervisory LED

• Shut off system piezo sounders

• Turn off appropriate zone relay output (ACM-8RF)

• Turn off supervisory relay

• Turn off all remote annunciator general supervisory alarm LEDs

• Turn off all remote annunciator zone supervisory alarm LEDs

Note that for any zone programmed for Supervisory auto-resettable, the Reset switch does not need to be pressed to
clear the zone (supervisory condition).

4.3.5 Trouble Condition Response

The control panel will perform the following upon detection of one or more trouble conditions:

• Blink the FACP trouble LED (1 second On, 1 second Off)

• Blink the Zone trouble LED if trouble condition is on the zone (1 second On, 1 second Off)

• Blink all annunciator general system trouble LEDs

• Blink all affected zone trouble LEDs on all system annunciators

• Activate trouble relay

• Store the trouble conditions in the Last Event/History File

• Sound system piezo sounders at a rate of 1 second On, 1 second Off

Note that when AC Brownout occurs, the AC LED is turned off and the Trouble LED blinks. Activation of the Trouble
relay is dependent on AC Loss Delay programming.

4.3.6 Trouble Condition Restoral

The control panel performs the following upon restoral of all trouble conditions:

• Shut off the trouble LED

• Shut off the zone trouble LED(s)

• Shut off the piezo sounder

• Deactivate the FACP trouble relay

• Turn on the AC power LED if the trouble was loss of AC power

• Turn off the system general trouble LED on all system annunciators if all trouble conditions are cleared

• Turn off all affected zone trouble LEDs on all system annunciators

Advertising